Electrical Input |
Voltage |
120 and 230 Vac Nominal; see Model Selection Guide for user-selectable voltages |
On Line Voltage Range |
+20% for nominal voltage at full load |
Nominal Input Frequency |
45-65 Hz, 50/60 Hz; auto-sensing |
Input Protection |
120 V models: Reset-able circuit breaker
230 V models: AC source overcurrent protection device (required) |
Connection |
120 V models: 6 ft. cord w/5-I5P
230 V models: IEC-320, 10A male connector |
Electrical Output |
Power Levels |
500-1400 VA |
Online Regulation |
-10%, +6% of nominal voltage |
On Battery Voltage Regulation |
+/-5% of nominal voltage; -10% after low battery warning |
On Battery Frequency Regulation |
+/-0.1 Hz of nominal frequency |
Voltage Wave Shape |
Sine wave (during normal and battery operation) |
Connections |
See Model Selection Guide |
Interconnecting Cords (230V models) |
2 ea. IEC-320, 10A |
Indicators and Controls |
Front Panel LEDs |
Power on, on battery, overload, and battery fault |
Front Panel Buttons |
On/Off and alarm silence/self-test |
Communications Port |
DB9 female (UPS ships with communications cable); USB Interface Adapter is optional |
Power Factor |
500 VA: 0.64
750/1000 VA: 0.67
1400 VA: 0.68 |
Battery |
Battery Type |
Sealed, maintenance-free lead-acid; starved electrolyte |
Battery Description |
500 VA: (1) 12 V, 9 Ah
750 VA: (2) 12 V, 7.2 Ah
1000 VA: (2) 12 V, 9 Ah
1400 VA: (3) 12 V, 9 Ah |
Battery Recharge |
< 3 hours to 90% capacity |
Battery Runtime |
5 minutes minimum; See Battery Runtimes table |
Start-On-Battery |
Startup with UPS batteries in absence of utility power |
General |
Topology |
Line-interactive |
Dimensions and Weight |
see Model Selection Guide |
Network Transient Protector |
In and out RJ11 jack for telephone/modem protection (120 V models only) or RJ45 for 10Base-T network cable; UL497A tested |
Environmental and safety |
Operating Temperature |
0oC to 40oC (32oF to 104oF) UL tested at 25oC (77oF) |
Safety Markings |
UL, cUL, and CSA; 230V models also CE and TUV |
Safety Conformance |
UL 1778, CAN/CSA C22.2, No. 107.1; 230 V models also EN 50091-1-1 and IEC 60950 |
EMC Markings |
FCC Class B; 230 V models also CE (EN50091-2) and C-Tick |
Surge Suppression |
ANSI C62.41 Category A (formerly IEEE 587) |
Immunity |
IEC 801-2, -3, -4 |
Transit/Storage Temp. |
-15ºC to 55ºC (5ºF to 131ºF) |
Audible Noise |
< 45 dBA typical |
Relative Humidity |
5-95% non-condensing |
* Due to continuing product improvement programs, specifications subject to change without notice
|